BATTERY
/ 2000 |
TM |
|
|
|
|
|
|
|
|
|
|
|
2M-12140-UPS (12V-475Watt) |
UPS/ TELECOM SERIES |
12V-140AH |
|
|
|
|
|
|
|
|
|
SPECIFICATIONS |
|
|
|
Nominal Voltage |
12 V |
|
|
|
Terminal Type |
Threaded
Copper Insert |
|
|
|
Max. Discharge
Current |
800A (5 sec) |
|
|
|
|
500A (continue) |
|
|
|
Terminal Type |
Threaded
Copper Insert |
|
|
|
Max. charge current |
|
42.0 Amps |
|
|
|
|
Weight |
46.5 kg (102.3
lbs.) |
|
|
|
Dimensions (approx) |
Length |
|
347
mm 13.61" |
|
|
|
Width |
173.5
mm 6.80" |
|
|
|
Height |
285.5
mm 11.19" |
|
|
|
Total Height |
287
mm 11.25" |
|
|
|
Plates |
Separator |
|
|
|
Lead Calcium alloy |
Micro porus Fiberglass |
|
|
|
Self
Discharge @ 77*F (25*C) |
|
|
|
Capacity after 3 months storage |
91% |
|
|
|
Capacity after 6 months storage |
82% |
|
|
|
Capacity after 12 months storage |
64% |
|
|
|
Capacity
affected by temperature (20 hr. rate) |
|
|
|
|
|
|
104*F (40*C) |
|
102% |
|
|
|
|
|
|
77*F (25*C) |
|
100% |
|
|
|
|
|
|
|
58*F (-15*C) |
|
65% |
|
|
|
Product
Features |
Capacity @ 77*F (25*C) |
|
|
|
Maintenance
Free. |
140.0Ah @ 20 hour rate to cut off 1.75v/c @ 25*
C. |
|
|
|
Sealed
Construction makes it spill proof. |
128.0Ah @ 10 hour rate to cut off 1.75v/c @ 25*
C. |
|
|
|
Vent system
automatically opens and reseals. |
122.0Ah @ 5
hour rate to cut off 1.70v/c
@25* C. |
|
|
10 year design life |
10 year
design life |
96.0Ah
@ 1 hour rate to cut off 1.55v/c @25*
C. |
|
|
|
Operates at
low internal pressure |
71.0Ah @ 15
min rate to cut off 1.67v/c @25* C. |
|
|
|
Flame
Retardant ABS housing |
Discharge |
-15oC to 50oC |
|
|
|
Battery will
operate in any position. |
Charge |
-35oC to 60oC |
|
|
|
Battery is 100% memory free |
|
|
|
Recommended |
-20oC to 25oC |
|
|
|
Absorbed glass mat technology |
|
|
Charging (constant voltage) |
|
|
|
for up to 99% efficient gas recombination |
|
Cycle use |
14.4- 14.7 volts @ (77*F) (25*C) |
|
|
|
|
Float use |
13.5
- 13.8 volts @ (77*F) (25*C) |
|
|
|
|
Storage |
9 months @
68*F (20*C) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Actual
Wattage/Amperage to discharge @ 25* C. |
|
|
vpc |
|
5 |
10 |
15 |
30 |
40 |
50 |
|
|
|
|
|
1.75 |
Watt |
749 |
568 |
469 |
294 |
227 |
203 |
|
|
|
|
25*C |
Amp |
428 |
325 |
267 |
168 |
135 |
116 |
|
|
|
|
1.67 |
Watt |
751 |
571 |
475 |
300 |
234 |
213 |
|
|
|
|
25°C |
Amp |
446 |
338 |
284 |
175 |
140 |
121 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|